Center-fed panelboards in dwellings

only applies to dwellings (Article 100)

705.12 (B)(3)(4): center-fed panels

Since there is no opposite of the middle… we apply the 120% rule to center-fed panelboards in dwellings

Can use 1 of the 2 ends – NOT both. Must pick 1 end. If you have >1 breaker you stack them up from the bottom.

Do not have to apply the label stating “do not relocate this overcurrent device” – not required but still good idea.