705.12(B)(3)(1): total sources don’t exceed busbar rating

(Imax X 1.25) + main supply OCPD <= Busbar rating

How big of an inverter can I connect? Rearrange the formula:

Imax <= (busbar rating – main supply OCPD) / 1.25

Example:

225 A busbar, 200 A main supply OCPD
Imax <= (225 A – 200 A ) / 1.25 = 20 A = 20
Imax <= 20 A

Therefore you can install UP TO a 20 A total inverter imax

705.12(B) Busbar ratings – SIX OPTIONS

1.
“100% rule”
125% of power source output current + primary source OCPD protecting busbar <= Ampacity of busbar

2.
“120% rule”
Two sources at opposite ends of busbar: 125% of power source output current + primary source output current + Primary source OCPD protecting busbar < = 120% of busbar ampacity
3.
“Inverter AC combiner panel”
Sum of ampere ratings of all load and power source OCPDs in panelboard <= Ampacity of busbar
4.
“Center-fed panel in dwelling”
This is same as option 2 above
5.
Engineering supervision for multiple-ampacity busbars
6.
Busbars in panelboards that supply lugs connected to feed-through conductors