705.12(B)(3)(6): panelboards supplying feed-through conductors

size feed-through conductors as feeders per 705.12(B)(1)

  • must consider both power sources – primary and interconnected
  • existing feed-through conductors may not have sufficient ampacity

There are 2 choices:

  • size fee-through conductors based on: main supply OCPD + (Imax X 1.25) OR
  • re-establish overcurrent protection at point of feed-through conductor supply